  VACUUM CIRCUIT BREAKER TYPE ABSVO-12 (INDOOR)
 

TECHNOLOGY:
The break - through of the Vacuum switching principle was essentially due to the development of an Interrupter that made it possible to use the vacuum circuit breaker for all the switching functions in system operation. It was the result of research on the arc quenching effects, on the most suitable material to be used and design and construction. The advantages offered by the vacuum switching principle make it the most economically efficient at present and the breaker superior to other designs:

  • Constant dielectric.
  • Constant contact resistance.
  • High total current switching.
  • High reliability.
   
  FEATURES:
     
 
  • Fully inter locked for high safety to the personals.
  • Reliable operation
  • Rigid design.
  • Compact.
  • Safe and easy horizontal isolation and horizontal draw-out within the breaker chamber.
  • Earthed metal partitions and shutters.
  • Guaranteed voltage withstand.
  • Access to cable from the rear of the panel.
  • Integral earth switch.
  • Uncomplicated and maintenance free Mechanism -AB100.
   
  CONSTRUCTION
xxx  

Panel housing

Panel housing for ABSVI-12 Circuit Breaker bolted construction made out of 3 mm CRCA sheets. The design is made to meet all the alternatives to suit customer applications.

This is an indoor metal clad design with air-insulated bus bars. The panel has compartmentalized with following to prevent secondary flash over in the event of power arc in any of the other departments.

  • Breaker compartment.
  • Instrument compartment.
  • Busbar compartment.
  • CT and Cable compartment.


   
  Circuit Breaker
 
 

Circuit breaker consists of motor or manual charged spring operating mechanism with 3 individual Vacuum interrupters actuated by common drive shaft arrangement.

The breaker has very high mechanical and electrical operating strengths.

Due to the simplicity of design totally maintenance free.

Breakers are ideally suitable for Arc furnace duties in addition to the feeder transformer capacitor bank etc.

   
  Spring operated Mechanism AB100
 
 
AB100 Mechanism used with vacuum breaker is of robust and reliable simple design. The linkages are easily accessible incase maintenance is required. Stored energy by the spring is used for closing and tripping operations. Spare charge is also possible for autoreclosure applications.
 
TECHNICAL DATA:  
Rated voltage (kV)
12
Power frequency withstand voltage(kV)
28
Impulse withstand voltage(kVp)
(1.2/50 Micro sec. Wave)
75
Rated current (A)
630/1250
Rated busbar current (A)
800/1250/2000
Symmetrical breaking current (kA)
25
Breaking current (peak kA)
63
Frequency (Hz)
50/60
Degree of protection (main enclosure)
IP4X
   
   
 
Note: Any accessory ,if required should be specified in addition to the above type reference.